Products

Eurotech Conventional Fire Alarm Panel

The Eurotech 8 control panel is housed in the most attractive, modern designed, flame retardent ABS enclosure, utilising a switch mode power supply. It has a fully removable front cover which improves ease of access for cable installations.

Optional Metal Backbox

The Eurotech 8 panel can also be ordered with a metal back box facilitating upto 7ah batteries to fit within the panel housing. To order this version add "/M" to the end of the model number (i.e. IN1/M, 1N2/M, etc.)

Features

  • Access via password - removes problem of lost keys
  • One man test facility
  • Disablement facility for zones Et sounders
  • Space for up to 3Ah batteries
  • Sounder delay option
  • 4 sounder circuits (1N4, 1N6 Et 1N8)
  • Sounder circuits 3 and/or 4 can be configured as Aux 24V supplies
  • Meets all requirements of latest EN54 part 2 and part4
Model Eurotech1 Eurotech2 Eurotech4 Eurotech6 Eurotech8
Part No 2500/1 2500/2 2500/4 2500/6 2500/8
Mains Voltage 230V AC +10% / -15% ® 50/60 Hz
System Voltage 24V DC (Nominal)
Zone Voltage 21V DC (Nominal)
Sounder Alarm Output 2 x 150nnA ® 24V DC 4 x 150mA ® 24V DC
Fault Relay1 x Volt Free Relay, SELV @ 1A Max
Fire Relay1 x Volt Free Relay, SELV ® 1A Max
Zone Capacity32 devices per zone
Remote sounder operationVia N/O contact connected to Class Change
Sounder Activation Delay0 to 10 minutes in 1 minute increments
Zone End of line1 N4002 Diode (Cathode Stripe to Zone +ve)
Sounder End of Line10K resistor
Charger Voltage27.6V
Battery cut offBattery voltage less than 20V
Battery Internal Resistance limit0.9 ohm
Enclosure size371 x 302 x 93 (mm)
Weight3 kg (Excluding Batteries)
Maximum battery space2 x 3.4 Ah, 12 Vdc sealed lead acid

We are happy to serve you @ 24/7